China’s AI server market is expanding rapidly in 2026, continuously driving explosive demand for liquid cooling. Boasting high heat dissipation efficiency and low PUE (Power Usage Effectiveness), liquid cooling has become the mainstream solution for high-end AI data centers. According to TrendForce forecasts, liquid cooling penetration in AI chips is expected to approach 60% by 2027, turning liquid cooling systems from an optional add-on into standard equipment. Nevertheless, precise temperature control of liquid cooling systems is critical to ensure stable chip operation, making calibration technology increasingly important.
A liquid cooling system mainly consists of Cooling Distribution Unit (CDU), liquid cold plates, circulating pipelines, water pumps, cooling towers and other components. The CDU distributes coolant to each cabinet. Cold plates attach directly to chips to remove heat. Circulating pipelines connect all compartments, pumps drive coolant flow, and cooling towers discharge heat outdoors. Temperature control of the whole system relies on high-precision temperature sensors installed on supply lines, return lines and chip surfaces. Their calibration accuracy directly affects heat dissipation performance and system safety. These temperature sensors act as the "nerve endings" of the system — accurate temperature readings determine whether chips will overheat and whether power costs will surge.
Three Key Temperature Measurement Points in Liquid Cooling Systems
1. Coolant Supply Temperature
Measurement location: Supply pipeline from CDU outlet to server cabinet
Temperature range: 15℃~35℃, accuracy requirement: ±0.1℃~±0.3℃
Importance: Directly affects chip cooling performance. Excessively high temperature causes thermal throttling or even system outage.
2. Coolant Return Temperature
Measurement location: Return pipeline from server cabinet outlet to CDU
Temperature range: 25℃~55℃, accuracy requirement: ±0.1℃~±0.3℃
Importance: Reflects actual server thermal load and enables dynamic cooling capacity adjustment.
Why Precise Calibration Is Required
1. Safeguard Equipment
Loss of temperature control in liquid cooling systems may push the chip junction temperature above 85°C, triggering thermal protection and even permanent damage. Accurate monitoring is the first line of defense against chip burnout.
2. Improve PUE
Precise regulation of supply temperature (e.g., raising from 20℃ to 25℃) reduces power consumption of CDU compressors and cuts PUE by 0.05~0.1. For large-scale data centers, every 1℃ improvement translates to millions in annual electricity savings.
3. Enable Predictive Maintenance
Temperature trend analysis can detect pump degradation, pipeline scaling or cold plate clogging in advance to prevent unexpected failures.
Fluke Metrology Wells 917X / 914X: Bring the Lab to the Field
✅ Highly portable for easy transport
No liquid medium required. Much lighter than liquid baths. One person can carry it into the data center.
✅ 5–10 times faster
Temperature stabilization time is 5 to 10 times faster than liquid baths. Jobs that used to take a full day can be finished within half a day.
✅ Dual-zone temperature control technology
Dual-zone control for upper and lower blocks. Stability up to ±0.005℃/±0.01℃. Axial uniformity reaches ±0.02℃/±0.05℃ within the 60 mm / 40 mm zone.